Schneider TAC Xenta 421A 0-073-0245-0 Universal Inputs & Relay Output ModuleSchneider TAC Xenta 421A 0-073-0245-0 Universal Inputs & Relay Output ModuleSchneider TAC Xenta 421A 0-073-0245-0 Universal Inputs & Relay Output ModuleSchneider TAC Xenta 421A 0-073-0245-0 Universal Inputs & Relay Output ModuleSchneider TAC Xenta 421A 0-073-0245-0 Universal Inputs & Relay Output ModuleSchneider TAC Xenta 421A 0-073-0245-0 Universal Inputs & Relay Output Module

1x Schneider TAC Xenta 421A 0-073-0245-0 Universal Inputs & Relay Output Module

Supply voltage (G, G0)  24 V AC ±20%, 50/60 Hz  21.6–40 V DC
Power consumption max 4 W
Transformer sizing  8 VA
Universal inputs (U1–U4):
A/D-resolution 12 bits
–as Digital Inputs;
Voltage across open contact  20 V DC
Current through closed contact  3 mA
Pulse input duration (TAC Menta CNT block) min. 20 ms
–as Thermistor Inputs;
TAC thermistor sensor  1800 ohms at 25 °C (77 °F)
Supply voltage 1 V DC
or (individually selectable)
TAC thermistor  10 kohms at 25 °C (77 °F)
Supply voltage  5 V DC
Measuring range –50 °C to +150 °C (–58 °F to 302 °F)
–as Current Inputs;
Input signal (terminals U–M; over-current protected) 0–20 mA
Input resistance   47 ohm
Inaccuracy within ± (0.03 mA + 0.4 % of reading)
–as Voltage Inputs;
Input signal  0–10 V DC
Input resistance   >100 kohm
Inaccuracy within ± (7 mV + 0.2 % of reading)
LED digital input status indicators (TAC Xenta 422A only)
Color red or green, selected using TAC Menta
Polarity  non-inverted or inverted, selected using TAC Menta
Digital outputs (K1–K5):
Control voltage, relay outputs  max. 2A, 250 V AC
Control current, to be protected by a max. 10 A fuse,
max 2 A (greater current allowed for short periods)
Pulse length  min. 0.5 s