Ignorer et passer au contenu

A1 Customer Oy

Skip to product information
1 sur 5

Schneider Electric TAC Xenta 103-A Contr Zone

Prix habituel
€180,00
Prix habituel
Prix soldé
€180,00
Schneider Electric TAC Xenta 103-A Contr ZoneSchneider Electric TAC Xenta 103-A Contr ZoneSchneider Electric TAC Xenta 103-A Contr ZoneSchneider Electric TAC Xenta 103-A Contr Zone
2x Schneider Electric TAC Xenta 103-A Contr Zone
Supply voltage 24 V AC –10% +20%, 50–60 Hz
Power consumption:
Controller with TAC Xenta OP 4 VA
Actuator supply max. 12 VA
Digital outputs max. 2×19 VA = 38 VA
Total max. 54 VA
Ambient Temperature
Storage –20 °C to +50 °C (–4 °F to 122 °F)
Operation 0 °C to +50 °C (+32 °F to 122 °F)
Humidity max. 90% RH non-condensing
Mechanical
Enclosure ABS/PC
Enclosure rating IP 30
Weight . 0.4 kg
Inputs/Outputs
Inputs X2–X3 for occupancy sensor and window contact:
Voltage across open contact 23 V DC ±1 V DC
Current through closed contact 4 mA
Minimum pulse input duration, inp. X2/X3 250 ms / 15 sec.
Outputs V1–V2 for heating valve actuators (triac):
Minimum output voltage supply voltage – 1.5 V
Maximum load 0.8 A
Input X1 for bypass button on wall module:
Minimum pulse input duration 250 ms
Maximum current, LED 2 mA, for ZS 100 series
Temperature sensor input B1:
Thermistor type NTC, 1800 W at 25 °C (77 °F)
Measuring range –10 °C to 50 °C (14 °F to 122 °F)
Accuracy ±0.2 °C (±0.36 °F)
Input R1, setpoint adjustment on wall module:
Type 10 kW linear potentiometer
Adjustment range ±5 °C (±9 °F)
Accuracy ±0.1 °C (±0.18 °F)
Input Z1, carbon dioxide sensor:
Measuring range 0–10 V DC
Accuracy ±0.05 V
Outputs Y1–Y2, cooling valve and cooling damper:
Output range 0–10 V DC
Maximum current 2 mA
Accuracy ±0.2 V
Application Program
Cycle time 6 sec.
Indication LED Colors
Power On green
Service red

price here is per lot
Sale

Unavailable

Sold Out