Festo CP-E16-M8-Z Input Module

ATEX-certified input module for use in explosive gas and dust atmospheres

Overview

This is a Festo CP-E16-M8-Z input module, an I/O module rated for use in potentially explosive atmospheres under ATEX Zone 2 (gas) and Zone 22 (dust) classifications. Designed with M8 connectivity, this module is suited to industrial automation applications requiring certified operation in hazardous locations where combustible gases or dust may be present.

Key Features

  • ATEX Zone 2/Zone 22 rated: Certified for use in gas (Zone 2) and dust (Zone 22) hazardous locations, categories II 3G and II 3D.
  • Defined ignition protection types: Ex nA IIC T5 X Gc for gas; Ex tc IIIC T80°C X Dc IP65 for dust.
  • Wide explosive ambient temperature range: Rated for -5°C ≤ Ta ≤ +50°C.
  • CE marked: Compliant with EU EMC directive and EU explosion protection directive (ATEX).
  • Multiple international certifications: KC EMC, C-Tick, and cULus Recognized (OL).
  • LABS (PWIS) conformity: Conforms to VDMA24364-B2-L for lubricant-free assembly systems compliance.

What's Included

Model Function Qty
CP-E16-M8-Z ATEX-rated input module 1

Model: CP-E16-M8-Z | Brand: Festo | ATEX Zone 2/22 Rated | CE Marked

Technical Specifications

Product type: CP-E16-M8-Z, input module.

LABS (PWIS) conformity: VDMA24364-B2-L.

CE marking: Per EU EMC directive and EU explosion protection directive (ATEX).

KC characters: KC EMC.

Certification: C-Tick, cULus Recognized (OL).

Explosion prevention and protection: Zone 2 (ATEX), Zone 22 (ATEX).

ATEX category (gas): II 3G.

ATEX category (dust): II 3D.

Type of ignition protection (gas): Ex nA IIC T5 X Gc.

Type of ignition protection (dust): Ex tc IIIC T80°C X Dc IP65.

Explosive ambient temperature: -5°C ≤ Ta ≤ +50°C.

Compatibility & Applications

This input module is suited to industrial automation applications requiring certified operation within ATEX Zone 2 (gas) or Zone 22 (dust) hazardous areas. Buyers should confirm the specific zone classification and ignition protection rating match their site's hazardous area classification, and ensure installation complies with applicable ATEX regulations for their jurisdiction, before use.